Description:
enEX has developed an air heat source heat pump to be used for sanitary hot water production in restaurants, hotels, hospitals, laundries, residential complexes, or sport centers.
Basic Specifications:
- Voltage supply: 380 V - 50 Hz
- Dimensions [mm]: 1400 x 800 x 1800
- Temp. water in range [°C]: 10-25
- Temp. water out range [°C]: 50-85
- Evaporator type: finned coil
- Gas cooler: forced circulation, single or double wall
- PS [bar]: 60/120
- Temp. outdoor air [°C]: -10 / +30
At Temp. in/out water 10°/65°C / Temp. outdoor air 5°C:
- Heating capacity [kW]: 22.4
- Power input [kW]: 5.4
- COP: 4.2
- Hot water production [l/min]: 5.82
Advantages:
- High temperature of water output: up to 90°C
- Low storage volumes through water heating in a single passage (once-through) passage and use of stratified storage tanks
- Low running costs through hot water production over night and lower energy costs
- Easy installation & servicing: only water and electrical power connection; programmable working times