AC70 Brazed plate heat exchanger
[ - ] Text [ + ]
Applications:
Heating
Refrigeration
Other

Partners: Alfa Laval

Contacts:

Piergiorgio Barbato, Italy
AC70 Brazed plate heat exchanger
Description

AC70 is the innovative Alfa Laval brazed heat exchanger specifically developed to work in air conditioning, refrigeration, and heat pump applications. AC70 is a single refrigerant circuit unit developed for chillers in the 10-80 kW range and heat pumps in the 5-40 kW range; it is suitable to work as an evaporator, condenser, and economizer. As ACH70 it can be used in CO2 cascade systems.

Possible applications

- Evaporator or condenser in chiller and heat pumps
- Economizer in chiller and heat pumps

Basic Specifications
  • Design temperature: -196°C / +150°C
  • AC70 design pressure: 32 bar
  • ACH70 design pressure: 45 bar
  • Volume per channel: 0.095 dm³
  • Maximum flow rate (water side): 14 m³/h
  • Dimensions: A = 10 + n x 2.3 (mm)
  • Weight: 2.3 + n x 0.17 (kg)   (n = number of plates)
Advantages
  • High reliability: tested in daily fatigue cycles during on/off operations
  • High quality level: patented integrated distributor pressed together with the plate to assure highest level of quality and performance reliability
  • Complies with major pressure vessel codes: PED (EU), UL (USA), KHK (Japan)